Model 5700 Installation and Operation Manual
7-8 151295
To map zone events to outputs, follow these steps:
1. From the Main Menu, select for Program Menu.
2. From the Program Menu, select for Zone.
3. From the next menu, select for Edit Zone.
4. Enter the zone number you wish to edit.
5. From the next menu, select for Zone Outputs.
6. From the next screen, a list of 8 event types will display. Select the event type you want to
program. A screen similar to the one shown in Figure 7-3 will display. Press .
7. Press the or key to toggle the group letter to either G = Group or T = output group
template depending on want you need for this zone. Press .
8. Select options for each event that could occur in this zone. Figure 7-3 is a complete exam-
ple of how you might map a zone.
Figure 7-3 Selecting Output Groups/templates and Cadence Patterns for a Zone Event
7
2
1
3
Indicates type of event (in
this case, Manual Pull alarm).
See Section 6.5 for choices.
Indicates output group 1, cadence
pattern 00 has been selected. 00 is
a constant output cadence. See
Section 7.3.1.4 for choices.
"T" Indicates output group
template 1. See Section 7.4.5 for
more information on output group
templates.