3.6.1.1 Current Draw Worksheet for SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation.
(Copy the page if additional space is required.)
Table 3-2: Current Calculation Worksheet
Device # of Devices Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
battery)
1
Standby: 200 mA 200 mA
Alarm: 325 mA 325 mA
Addressable SLC Devices
SD500-AIM
(50 max.)
1
Standby/Alarm: 0.55 mA
mA mA
SD500-MIM mA mA
SD500-ARM mA mA
SD500-PS/SD500-PSDA mA mA
SD500-AIS
SD505-AHS mA mA
SD505-APS mA mA
SD505-ADHR
(50 max.)
Aux. Pwr
Standby: 35 mA
2
mA
Alarm: 75 mA
2
mA
SLC
Standby/
Alarm: .082 mA
mA mA
SD505-DTS None, included with SD505-ADHR worst case.
SD505-ADH None, included with detector current.
SD500-ANM
(50 max.)
1
Aux. Pwr
Standby: 8 mA mA
Alarm: 60 mA mA
SLC
Standby/
Alarm: .55 mA
mA mA
SD500-LED
(50 max.)
1
Aux. Pwr
Standby: 10 mA mA
Alarm: 220 mA mA
LED: 10 mA mA mA
SLC
Standby/
Alarm: 0.55 mA
mA mA
SD500-SDM
(50 max.)
1
Aux. Pwr
Standby: 20 mA mA
Alarm: 106 mA mA
SLC
Standby/
Alarm: .55 mA
mA mA
SLC Accessory Bases
SD505-6RB (50 max.) Standby/Alarm: .082 mA mA mA
SD505-6SB (50 max.)
Aux. Pwr
Standby: 1 mA mA
Alarm: 32 mA mA
SLC
Standby/
Alarm: .082 mA
mA mA
SLC Isolator Devices
SD505-LIM
(100 max.)
Standby/Alarm 0.092 mA mA mA
SD505-6IB (50 max.)