SILENT KNIGHT INTELLIKNIGHT 5808 Especificaciones Pagina 142

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 141
System Operation 151274-L8
8-16
8.7.1 Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors, and a designated manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts the user that the
initial stages required for a release condition are present. (Also refer to Table 8-3.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the “Release” outputs
will activate and the “Pre-Alarm” output will deactivate. (Also refer to Table 8-3.)
Reduce detector spacing to 0.7 times the linear spacing in accordance with NFPA 72.
Note: Refer to Table 8-2 for approved releasing solenoids and ratings.
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Table 8-3: Single Interlock Zone Operation
Inputs Output Results
1st Addressable Detector
X X X X
2nd Addressable Detector
X X X X
Manual Release Station
X X X X
Normal
Pre-Alert
Pre-Alert
Release and General Alarm
Release and General Alarm
Release and General Alarm
Release and General Alarm
Release and General Alarm
Vista de pagina 141
1 2 ... 137 138 139 140 141 142 143 144 145 146 147 ... 179 180

Comentarios a estos manuales

Sin comentarios