IntelliKnight 5808 Installation Manual 151274-L8
7-7
Zone Mapping Example
Suppose you want to program Zone 1 so that:
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the ANSI cadence
pattern.
Manual pull alarm would activate Output Group 3 using constant output.
Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output groups. Figure 7-5
shows how you would program this application.
Figure 7-5 Zone Mapping Example