SILENT KNIGHT INTELLIKNIGHT 5808 Especificaciones Pagina 173

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 172
IntelliKnight 5808 Installation Manual 151274-L8
A-13
A.3 Compatible 520Hz Low Frequency Bases
System Sensor 1400 A N/A 20 / loop
1451 (B401B) A A 20 / loop
2100 A N/A 20 / loop
2100T A N/A 20 / loop
2151 (B401) A N/A 16 / loop
2151T (B401) A N/A 16 / loop
2300T A N/A 20 / loop
2300 A N/A 20 / loop
2300TB A N/A 20 / loop
2400 A N/A 20 / loop
2400 (DH400) A N/A 20 / loop
2400AIT A N/A 20 / loop
2400AT A N/A 20 / loop
2400TH A N/A 20 / loop
2451 (B401B) A N/A 20 / loop
2451DH (DH 400) A N/A 20 / loop
2451TH (B401B) A N/A 20 / loop
2W-B A N/A 16 / loop
2WT-B A N/A 16 / loop
2WTR-B A N/A 16 / loop
Table A-3 Low Frequency Bases
Model Number Description
B200S-LF Low Frequency Intelligent Sounder Base
B200SR-LF Low Frequency Intelligent Sounder Base
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
Model Name or Number
(Base model name or number
in parentheses.)
Compatibility ID
# per Loop
Head Base