SILENT KNIGHT INTELLIKNIGHT 5808 Especificaciones Pagina 53

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 52
Control Panel Installation 151274-L8
4-24
power is immediately restored to the door holder circuits.
Figure 4-29 Example of an Auxiliary Power For Door Holder
Note: Figure 4-29 uses UL listed door holder Model 1400 from Door Control International as an example.
4.11.2.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at
Constant circuits.
4.11.2.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke
detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system
reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied.
4.11.2.4 Sounder Sync Power
Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use
with B200S sounder bases.
Supervised
Power Limited.
Special Application.
Vista de pagina 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 179 180

Comentarios a estos manuales

Sin comentarios