Installation Instructions
151174 3-7
3.5 Wiring Instructions
The following section contains information necessary to properly wire the Model 5000 Entry
System.
3.5.1 Power Requirements
The 5083 and 5084 main units are powered from a UL listed Class II, 16.5 VAC 40 VA
transformer that plugs directly into a 120 VAC 60Hz wall outlet. The transformer provides
power for the 5083 and 5084 main units and charging current for the 12 VDC backup battery.
In the event of a power outage, the 12 VDC, 1.2 AH battery (shipped with the unit) will
provide enough current to run the system for a minimum of 2 hours. The actual time will
depend on how much the system is used. All programmed data will be stored in Flash memory
if AC power is lost and the backup battery becomes depleted.
3.5.2 Installing the AC Transformer
Wire the transformer (Model 9220) to terminals 1 and 2 on the 5083 and 5084 printed circuit
board. Use 16-gauge or larger (14, 12, etc.) shielded wire. Ground the shield to terminal #3 on
the 5083 or 5084 and to the center screw terminal on the transformer as shown in Figure 3-5.
Also verify that the outlet is a non-switching circuit.
Figure 3-5 AC Transformer Wiring Diagram