Programming
150966 6-25
**Note:Both Silent and Invisible must be selected if the system must not have any audible or visual response as
in a typical Holdup zone
Bell If Dialer
Fails
If this option is enabled, there will be no bell or external speaker output unless the dialer
generates a fail event for this zone. The fail event will be generated when the dialer
exhausts the programmed number of attempts. This option does not affect the internal
speaker and will not cause any audible signals if the zone is also selected as a silent alarm.
This option must be disabled in a UL listed installation.
Disabled
Bell
Shutdown in
Alarm
If this option is enabled, an audible alarm will shut down after the programmed duration
has expired. Any new alarm restarts the delay. (Duration is programmed in the partitions
menu.)
Enabled
Local Zone Alarms for this zone can be sounded locally but there will be no reporting to the central
station. This option cannot be selected for any zone in a UL listed central station system.
Disabled
Chime
Enabled
Use this option to enable the chime feature for this zone.
When the chime feature is enabled (system must be disarmed), the key turns the
chime feature on and off. When the chime feature is turned on, a chime tone will sound at
the Touchpad when someone enters a chime zone (typically a door).
Disabled
Exit Delayed
Zone
This option enables the exit delay, a time period that allows the user to exit the premises
after the system has been armed. The duration of the delay is programmed in the area
menu.
The zone must be Ready before the system is armed and when the exit delay period
expires, but it may be in any other state during the exit delay period.
Disabled
Zone area
assignment
Select the area(s) that this zone will be assigned to. Zones can be assigned to more than
one area (but only to one partition).
Area 1
Zone
Response
(Armed and
Disarmed)
Select the system response for each zone input state when the zone is armed and disarmed.
You must select a response for all possible input states (shown below).
Possible input states for a zone are:
Input terminals are short circuited
EOL appears at the input terminals
Input terminals are open circuited
Possible responses to a zone input state are:
Alarm
Ready
Not Ready
Trouble
See Section 4.15 for more information.
Armed
Response
Short:
Alarm
EOL: Ready
Open:
Ready
Disarmed
Response
Short: Not
Ready
EOL: Ready
Open:
Ready
Table 6-7: Zones Screen Options and Descriptions