Programming
150966 6-29
Auto Test
Schedule
Select the time schedule that will control when the dialer will generate a
communication test signal. The communication occurs at the beginning of the
selected time window.
See Section 6.3.3 for more information about time schedules.
Report Tests must be selected in the Events to Report option in order for selection
here to take effect.
Never
Attempts Before
Switching
Enter the number of attempts the dialer will try to report to this account before
switching to the next account. Events are moved to a backup account (if any exists)
before switching. Range is 0 - 15. In a UL listed installation, select 5-10.
10
Attempts Before
Account Fail
Enter the number of attempts that the dialer will make for this account before an
account trouble event is generated. Account trouble events can be used by
programmable I/O and are used by the system to make zones audible that are
selected to be audible only if the communicator fails.
The account will have no further attempts until a new event occurs. Events in the
account are moved to a backup account (if any exists). Range is 0 - 99.
10
Reporting Format Select the reporting format that will be used for this account. Options are: SIA-20
SIA-20 Sends a maximum of 20 events in a single call. Sends only
one account number per call. This format must be used with
Silent Knight’s Model 9000 Receiver.
SIA-500 Can send up to 500 bytes in a single call. Sends data from
multiple accounts in a single call.
Contact ID Ademco format
ASCII Used with a printer.
Numeric Pager Sends Contact ID to a numeric pager.
Table 6-9: Reporting Accounts Options and Description
Option Description Default