Control Panel Description and Installation
150964 4-23
State of Zone
Programmed
Disarmed Response
Programmed
Armed Response
Open Circuit
Open circuit hardware
fault.
Trouble Trouble
EOL Circuit
The contact is open and su-
pervised.
Ready Ready
Short Circuit
The contact is closed or
there is a short circuit hard-
ware fault.
Alarm Alarm
Open Circuit
The contact is open or
there is an open circuit
hardware fault.
Not Ready Alarm
EOL Circuit
The contact is closed and
supervised.
Ready Ready
Short Circuit
Short circuit hardware
fault.
Trouble Alarm